Welding Cable Size And Voltage Drop Calculator

This calculator estimates the voltage lost in a welding machine’s electrode and return leads, from the cable size, the length of each lead, the welding current and the cable temperature. It shows the drop in volts, as a share of the arc voltage, and the heat wasted in the cable.

  • Free, no sign-up
  • Runs in your browser
  • Built for Islamabad & Rawalpindi

This free calculator runs in your browser and needs JavaScript. If it does not load, call or WhatsApp us on +92 304 2435577 and we will do the calculation for you.

On site, leads often get extended to reach the work. Each extra metre adds resistance, and the voltage lost in the cable is voltage the arc does not get. Above about 4 V the arc becomes noticeably harder to control. Sizing the cable for the length, not just the current, avoids that.

What This Tool Does

It adds the electrode lead and return lead lengths, since current flows out through one and back through the other, calculates resistance from the conductor resistivity corrected to the cable temperature, and multiplies by the current.

Who It Is For

  • Site welders running long leads.
  • Workshops buying welding cable.
  • Supervisors diagnosing a weak arc on a long lead.

How To Use It

  1. Choose copper or aluminium cable and the size printed on the sheath.
  2. Enter the electrode lead length and the return (earth) lead length.
  3. Enter the welding current and a realistic cable temperature.
  4. Enter the arc voltage to see the drop as a percentage.
  5. Click Check voltage drop.

Inputs And Units Explained

  • Cable size — conductor cross-section in mm². Cheap cable can be undersized; a quick check is the conductor diameter.
  • Both leads — the circuit length is electrode lead plus return lead.
  • Temperature — resistance rises about 0.4% per °C.

How The Calculation Works

Resistivity at temperature: ρ = ρ₂₀ × (1 + α × (T − 20)), with ρ₂₀ = 0.01724 Ω·mm²/m and α = 0.00393 for copper, ρ₂₀ = 0.02826 and α = 0.00403 for aluminium. Resistance R = ρ × total length ÷ area. Voltage drop = R × current. Heat in the cable = drop × current.

Worked Example

35 mm² copper cable, 15 m electrode lead and 10 m return lead, 200 A, cable at 40 °C, arc voltage 26 V.

Input or result Value
Total circuit 25 m
Resistance 13.28 mΩ
Voltage drop 2.66 V, 10.2% of the arc voltage
Heat in the cables about 530 W

Double both leads to 50 m in total and the drop passes 5 V. At that point a 50 mm² cable is the better choice.

Features And Benefits

  • Counts both leads.
  • Temperature-corrected resistance.
  • Drop as a percentage of the arc voltage.

Assumptions And Accuracy Limits

  • Connections, lugs, the work clamp and the work itself add resistance that is not included.
  • Current rating and duty of the cable come from the cable maker.
  • Aluminium cable needs suitable connectors.

Frequently Asked Questions

What size welding cable do I need?

It depends on current, duty cycle and total lead length. Check the voltage drop for your length here and the current rating in the cable maker’s table.

Does welding cable length affect the weld?

Yes. Longer cable means more voltage drop, which weakens the arc. Use a bigger cable for long runs.

Why count both leads?

The welding current flows out through the electrode lead and back through the return lead, so both carry the full current.

Is aluminium welding cable OK?

It works but has about 1.6 times the resistance of copper for the same size, so it needs a larger section.